Jump directly to main navigation Jump directly to content

Details on the Dialog “Attractions Table”

Information on the dialog Attractions dialog in the calculation method VDI 2089-1 Swimming Pools of the module Ventilation in LINEAR Building.

In this dialog, you define the water attractions of swimming pools and white water channels.

You are here

Module OverviewVentilationProject, Building Part, Storey, Area Level (Building Structure)Air VolumesCalculation Method ...VDI 2089-1 Swimming Pools (Selection of Calculation Method)Room LevelIndoor Swimming PoolsIndoor Swimming Pool (Selection of Room Type according to VDI 2089-1) (Column A)

“swimming pool halls” area of the swimming pool hall room type in the Ventilation module of LINEAR Building.

Enter the corresponding number of the respective attractions of the swimming pool or the white water channel so that the evaporated water mass flows caused by the attractions are taken into account when determining the air volume. Taking into account the relative field enhancement of the individual attractions, the water transfer coefficient of the attractions Δβ_A is determined and displayed in the corresponding column of the Swimming Pools or Slides and White Water Channels area.

Note: Only children's slides up to a slide length of 10 m are covered.

For water mushrooms, the circumference of the mushroom must be entered in addition to the number. The Water Mushroom Perimeter input field is activated as soon as a value is entered in the Water Mushroom input field.

Note: In the case of attractions with aerated water flows, you must enter the aeration mass flow of the attractions in the M_L column and the water vapor content of the aeration mass flow in the x_D.W column so that the water vapor discharge of the aeration flows is taken into account when determining the air volume.