Jump directly to main navigation Jump directly to content

Details on Dimensioning in Basic Conditions

Information about the section Dimensioning in the Basic conditions dialog in the Pipe Network Calculation Heating.

You are here:

Project tabDiscipline Planning typeAnalyse tabCalculation ...Basic conditions...

Applies to: Heating and Cooling.

Dialog basic conditions Linear Revit

Select if the calculation process is supposed be carried out according to maximum velocity, maximum pipe friction pressure gradient or maximum pipe friction pressure gradient dependent on the nominal diameter. The maximum velocity and the maximum pipe friction pressure gradient may be used at the same time.

If dimensioning is done according to maximum velocity and maximum pipe friction pressure gradient and one of the limit values is exceeded in a section part, the program automatically selects the next greater dimension.

Note:

If a section part has been assigned different limit values for maximum velocity and maximum pipe friction pressure gradient using command is Section part data or Editing section part data via drawing, these individual limit values have priority over settings specified in the Basic conditions dialog.

Max. velocity

Enabled: During dimensioning, limit values from the fields Max velocity and Max velocity in radiator connection pipes is used. The limit value Max. velocity is valid for all section parts except for radiator connection pipes. If the limit value for maximum velocity is exceeded in one section part, the next greater dimension is selected by the program.

Disabled: Dimensioning is carried out considering only pipe friction pressure gradients.

Max velocity in radiator connection pipes

Enter a separate limit value for maximum velocity in radiator connection pipes. It will be used if the checkbox Max velocity is active. If the limit value for maximum velocity is exceeded in a radiator connection pipe, the next greater dimension is selected by the program.

Max. pipe friction pressure gradient

Enabled: During dimensioning, the provided limit value for maximum pipe friction pressure gradient is used.

Max pipe friction pressure gradient dependent on the nom. diameter

Enabled: In the fields from DN and to DN, enter the nominal diameter range, within which the maximum pipe friction pressure gradient is valid.

Global pressure loss for fittings and joining pieces

The percentage of pipe pressure loss used to calculate pressure losses for fittings and jointing pieces. If 0 % is entered, the zeta values of the constructed form and connection pieces are used in the drawing.