Details on Technical Data for Buffer Storage

Information about the technical data dialog for buffer storage.

You are here:

Project tabDisciplineAnalyse tabComponentsTechnical data ...Component

Technical data buffer storage Linear Revit

Name

Specifies the name of the component. You can modify the name. Clicking restores the default setting.

Settings

The buffer storage performs like the hydraulic separator. It ensures a hydraulic separation of the pipe network and, thus, a separation of the flow paths. In both the primary circuit and the secondary circuit a pump must be installed. In the technical data, the required minimum diameter is determined via the maximum velocity and will be displayed among calculated components. The mass flow rate supplement may be entered freely but is set to a default value of 5%, which effects a minor temperature change in the connected supply water and return water pipes of the primary circuit. The new components hydraulic separator and pressureless manifold work similarly. The buffer storage is installed between supply water pipe and return water pipe.